70 S611 Soft Starter    MN03902011E—May 2012    www.eaton.com
Modbus Map, continued
Modbus 
Coil Number
Modbus
Register Number R/W DCI Descriptor Notes
— 402 R/W DCI_COMMAND_REGISTER 1 = Clear motor run hours
2 = Clear motor start count
3 = Clear fault queue
— 403 R/W DCI_CONFIGURATION_RESET 1 = Soft reset
2 = Factory defaults
— 404 R/W DCI_OVERLOAD_FLA Amps * 10
— 405 R/W DCI_MOTOR_RATED_VOLTAGE Volts, 115–600, (Default = 480)
— 406 R/W DCI_START_METHOD 0 = Vramp
1 = Limit
2 = Pump
— 407 R/W DCI_START_TIME Seconds*10, 0.5–180 (20)
— 408 R/W DCI_INITIAL_TORQUE %, 0–100 (45)
— 409 R/W DCI_STOP_TIME Seconds*10, 0–120 (0, no pump stop option, 50 
with pump stop enabled)
— 410 R/W Reserved —
— 411 R/W DCI_KICK_START_TIME Seconds*10, 0–2 (0)
— 412 R/W DCI_KICK_START_TORQUE %, 0–100 (0)
— 413 R/W DCI_RESET_MODE 0 = Manual
1 = Auto
— 414 R/W DCI_ENABLE_DISABLE_TRIP —
6609 — — Overload —
6610 — — Jam —
6611 — — Stall —
6612 — — Current Imbalance —
6613 — — Load Disconnect —
6614 — — Phase Loss —
6615 — — Under Voltage —
6616 — — Over Voltage —
6617 — — Voltage Unbalance —
6618 — — Phase Reversal —
6619 — — Ground Fault —
6620 — — Overload On Start —
6621 — — Shorted SCR —
6622 — — SCR Not Firing —
6623 — — Over Temp —
6624 — — — —
— 415 R/W DCI_OVERLOAD_TRIP_CLASS 5–30, (20)
— 416 R/W DCI_JAM_TRIP_LEVEL %FLA, 150–400 (300)
— 417 R/W DCI_JAM_TRIP_DELAY_SECONDS Seconds 1–20 (2)
— 418 R/W DCI_STALL_TRIP_LEVEL %FLA, 150–300 (200)