72 S611 Soft Starter MN03902011E—May 2012 www.eaton.com
Modbus Map, continued
Modbus
Coil Number
Modbus
Register Number R/W DCI Descriptor Notes
— 442 R/W DCI_MODBUS_PARITY 0 = Even parity, 1 stop bit (default)
1 = Odd parity, 1 stop bit
2 = No parity, 2 stop bits
3 = Even parity, 2 stop bits
4 = Odd parity, 2 stop bits
5 = No parity, 1 stop bit
— 443 R/W DCI_COMM_LOSS_TIMEOUT_MILLISECS Milliseconds, 1–65000 (2000)
— 444 R/W DCI_COMM_LOSS_BEHAVIOR 1 = Fault (default)
2 = Hold last state
3 = Stop
— 445 R/W DCI_NETWORK_WATCHDOG_ENABLE 0 = Disable
1 = Enable (0)