Startup_GTB116-P_r1a Page 2 of 2
Modbus Registers supported by this device.
11. If the Ethernet network connection is required continue to step 12, otherwise skip to step 14.
12. Press the ↑↓ arrow buttons simultaneously to enter the MAIN MENU. The SETTINGS menu is
displayed. Press the ENT button to select the top of the SETTINGS submenu category. Press the ↓
button until the ETHERNET submenu category is visible. Press the ENT button again to enter the
ETHERNET submenu. Configure the network parameters and press the ESC button twice to return
to normal operation.
GTB116 transmitters support simultaneous communication via BACnet IP or BACnet Ethernet,
Modbus TCP, and TCP/IP.
13. Refer to the Operations and Maintenance Manual for detailed information on the BACnet Objects and
Modbus Registers supported by this device.
14. Startup is complete! If additional customization is desired, consult the Operation and Maintenance
Manual.
VERIFICATION
Many installations require third-party airflow verification. If the airflow measuring device is within the
measurement uncertainty of the verification technique, EBTRON strongly recommends that no field
adjustment correction is made. EBTRON airflow measurement devices are factory calibrated to NIST
traceable standards. Field adjustment is not recommended when installed in accordance to published
guidelines.
If field adjustment is required, refer to the Operation and Maintenance Manual.
If minimum placement guidelines cannot be achieved, installed accuracy may be compromised.
Transmitters can be field adjusted to match a third-party measurement. Adjusted field measurements
typically result in comparative readings within ±3% of the third-party measurement. Be advised that
the third-party measurement may have uncertainties greater than or equal to ±10% and should only
be used to adjust the airflow measurement device if the probes do not meet minimum placement
requirements or the discrepancy is greater than the uncertainty of the third-party source.
FOR MORE INFORMATION ….
Operations and Maintenance Manual.
The Operations and Maintenance Manual is a comprehensive reference document that contains
information on installation, startup, custom configuration, built-in tools, diagnostics, troubleshooting and
maintenance.
NEED MORE HELP?
EBTRON Customer Service
For toll-free factory support call 1-800-2EBTRON (1-800-232-8766), Monday through Thursday 8:00 AM
to 4:30 PM and Friday 8:00 AM to 2:00 PM eastern time.
Your Local EBTRON Representative
Visit EBTRON.com for the name and contact information of your local representative.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ebtron Advantage IV Series and is the answer not in the manual?

Ebtron Advantage IV Series Specifications

General IconGeneral
BrandEbtron
ModelAdvantage IV Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals