Table 2 Inverter Mode Specifications
MODEL 6.5KW
Rated Output Power 6,500W
Output Voltage Waveform Pure Sine Wave <3% THD
Output Voltage Regulation 120Vac±5%
Output Frequency 60Hz or 50Hz
Peak Efficiency 91%
Overload Protection 100ms@≥205% load;5s@≥150% load; 10s@110%~150% load
Surge Capacity
13,000W
Nominal DC Input Voltage 48.0Vdc
Cold Start Voltage 46.0Vdc
Low DC Warning Voltage
@ load < 20%
46.0Vdc
@ 20% ≤ load < 50%
42.8Vdc
@ load ≥ 50%
40.4Vdc
Low DC Warning Return Voltage
@ load < 20%
48.0Vdc
@ 20% ≤ load < 50%
44.8Vdc
@ load ≥ 50%
42.4Vdc
Low DC Cut-off Voltage
@ load < 20%
44.0Vdc
@ 20% ≤ load < 50%
40.8Vdc
@ load ≥ 50%
38.4Vdc
64.0Vdc
High DC Cut-off Voltage 66.0Vdc
DC Voltage Accuracy
+/-0.3V@ no load
THDV <5% for linear load,<10% for non-linear load @ nominal voltage
DC Offset
≦100mV