User Manual – 5-20kVA Modular UPS

Table of Contents

Questions and Answers

  • C
    Christopher FisherSep 3, 2025
    What to do if Emerson Liebert APS UPS displays 'All PMs Are Not Ready'?
    • W
      Wendy NielsenSep 3, 2025
      If your Emerson UPS displays 'All PMs Are Not Ready', it means that the power module is not ready, and the yellow fault LED is flashing. Ensure that the power module is fully inserted in the upper frame bays and locking levers are in the locked position. If this does not resolve the issue, contact your local Liebert Service representative.
  • K
    krobinsonSep 2, 2025
    How to fix 'No Matching Module' error on Emerson Liebert APS?
    • B
      barryjacksonSep 2, 2025
      If your Emerson UPS displays 'No Matching Module', it means only one battery module is inserted into one layer of bays in the system. Ensure that there are a pair of battery modules in the same layer of the frame.
  • J
    joelberrySep 1, 2025
    What does Transformer Temperature Warning mean on my Emerson Liebert APS?
    • D
      David CollinsSep 2, 2025
      If your Emerson UPS is showing 'Transformer Temperature Warning', it means a high temperature condition has occurred in the output transformer area. Check the air filters located behind the bezels and clean them if necessary, or check to see if the ambient temperature is too high. If the problem persists, contact your local Liebert Service representative.
  • V
    Victor AdamsAug 31, 2025
    Why does my Emerson Liebert APS say 'Insufficient Capacity To Start Inverter'?
    • M
      Ms. Karina SmithSep 1, 2025
      If your Emerson UPS displays 'Insufficient Capacity To Start Inverter', it indicates that the load value exceeds the maximum load capacity of all operating modules. Ensure all power modules are inserted and the locking lever is fully inserted. If all modules are active, add power modules to increase capacity.
  • C
    Cheryl KirbyAug 30, 2025
    What to do if Emerson UPS says 'No Battery Modules Are Ready'?
    • E
      Edward SantiagoAug 31, 2025
      If the Emerson UPS displays 'No Battery Modules Are Ready', it indicates that the battery module is not ready, and the yellow fault LED is flashing. Ensure that the battery module is fully inserted and the locking levers are in the locked position. If the problem continues, contact your local Liebert Service representative.
  • S
    Sean OrozcoAug 29, 2025
    What does 'Battery Test Warning Weak Battery' mean on my Emerson UPS, and what should I do?
    • S
      Summer LewisAug 29, 2025
      If your Emerson UPS shows a 'Battery Test Warning Weak Battery' message, it means one or more battery modules has detected batteries that are no longer in specification due to age or operating conditions. Replace the battery string.
  • J
    Jordan BrownAug 29, 2025
    What causes BM Over Temperature Warning on Emerson UPS, and how can I fix it?
    • C
      Christopher ThomasAug 29, 2025
      If the Emerson UPS displays 'BM Over Temperature Warning', it indicates that the internal battery module temperature is at an elevated level. Check the air filters located behind the bezels and clean them if necessary. Also, verify that the ambient temperature is not too high. If the problem persists, contact your local Liebert Service representative.
  • M
    michelle82Aug 28, 2025
    How to troubleshoot Power Module Fan Failure on Emerson UPS?
    • N
      Nathan NelsonAug 28, 2025
      If you see 'Power Module Fan Failure' on your Emerson UPS, it means one or more of the power module fans has failed. Check to see if the fan is blocked. If it is not blocked, contact your local Liebert Service representative.
  • J
    Joseph PopeAug 27, 2025
    What to do if Emerson UPS output exceeds max load setting?
    • R
      ronald84Aug 27, 2025
      If your Emerson UPS displays 'Output Exceeds Max Load Setting', it means the actual load is larger than the maximum load alarm setting. You can either decrease the load on the UPS or readjust the user programmable alarm set point from the LCD. You might also need another power module to increase capacity.
  • J
    Jennifer LozanoAug 26, 2025
    How to resolve 'Time to Check the Fan Filters for Excessive Dirt' on Emerson Liebert APS?
    • T
      Teresa LaraAug 27, 2025
      If your Emerson UPS indicates 'Time to Check the Fan Filters for Excessive Dirt', it means that the air filter reminder is enabled. Inspect the air filters and clean them if necessary, or contact your local Liebert Service personnel.

Summary

Product Introduction

System Description

Provides an overview of the modular UPS system's purpose, capabilities, and adaptability.

Features

Lists the key features and advantages of the Liebert APS UPS system.

Operating Principle

Explains the fundamental operating principles of the Liebert APS UPS.

Operating Modes

Details the different operating modes the UPS can function in.

Major Components

Describes the main components of the Liebert APS UPS system.

Installation

Unpacking Inspection

Instructions for checking the UPS upon delivery for damage or discrepancies.

Installation Environment

Specifies the required environmental conditions for UPS installation.

Installation Tools

Lists the necessary tools for setting up the UPS.

Installation Site

Guidelines for selecting an appropriate installation site for the UPS.

Unloading the UPS

Procedures for safely unloading the heavy UPS unit from its pallet.

Mechanical Installation

Guides for the physical installation of the UPS unit.

Module Installation

Instructions for installing various modules into the UPS frame.

Cable Connection

Detailed procedures for connecting input and output power cables.

Commissioning;Startup Procedures

Procedures for initial UPS system startup and commissioning.

Communication

Liebert IntelliSlot Ports

Describes the Liebert IntelliSlot ports for communication options.

Dry Contact Ports

Explains the function and pin definition of dry contact ports.

REPO (Remote Emergency Power Off)

Details the REPO connection for remote emergency power off.

Long Run Time (LRT) Battery Temperature Probe Terminals

Information on connecting temperature probes for battery management.

USB Port

Describes the USB port for monitoring and connectivity.

Liebert MultiLink

Information about Liebert MultiLink software for UPS monitoring and control.

LCD Port

Details the LCD port for communication with the display module.

Operation and Display Panel

Overview

Provides an overview of the UPS display panel and its components.

LCD Screen

Describes the various screens and displays available on the LCD.

LCD Screen Views

Gives detailed descriptions of each display screen and its contents.

Entering a Password

Instructions on how to enter the control password for settings access.

Setting or Changing a Parameter Setting

Explains how to modify UPS operational parameters through the menu.

Troubleshooting

Active Alarms

Lists possible alarm messages and their corrective actions.

Module Troubleshooting

Guides on troubleshooting issues with UPS modules using LED indicators.

Module Replacement

Provides procedures for replacing or adding UPS modules.

Maintenance

Proper Care

Recommendations for optimal UPS maintenance and care.

Scheduled Maintenance

Outlines recommended monthly and annual maintenance tasks.

Cleaning Fan Filters

Procedures for cleaning or replacing UPS fan filters.

Specifications

Estimated Battery Run Times

Tables providing estimated battery run times based on load and battery configuration.

Tables for UPS Model Number Digits 1-3 are AS1 or ASA

Battery run time tables for specific AS1/ASA model numbers.

Tables for UPS Model Number Where Digits 1-3 are AS2 or ASB

Battery run time tables for specific AS2/ASB model numbers.

Tables for UPS model number digits 1-3 are AS3 or ASC

Battery run time tables for specific AS3/ASC model numbers.

Tables for UPS Model Number Where Digits 1-3 are AS4 or ASD

Battery run time tables for specific AS4/ASD model numbers.

Tables for UPS Model Number Where Digits 1-3 are AS5 or ASE

Battery run time tables for specific AS5/ASE model numbers.

Emerson Liebert APS Specifications

General IconGeneral
ModelLiebert APS
CategoryUPS
DimensionsVaries by model
WeightVaries by model
Input VoltageVaries by model
Input Frequency50/60 Hz
Output VoltageVaries by model
Output Frequency50/60 Hz
Form FactorVaries by model
TopologyVaries by model
EfficiencyVaries by model
Battery TypeVaries by model
Battery VoltageVaries by model
RuntimeVaries by model
Communication InterfaceVaries by model
Operating Temperature0° to 40°C (32° to 104°F)
HumidityVaries by model

Related product manuals