8.2.2 Configure Lower Range Value (LRV) and Upper Range Value
(URV) for the mA Output
Display Menu > Configuration > Inputs/Outputs > Channel x > I/O Settings > Lower Range Value
ProLink III Device Tools > Configuration > I/O > Outputs > mA Output > Lower Range Value
Device Tools > Configuration > I/O > Outputs > mA Output > Upper Range Value
Field Communicator Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mA Output xSettings > Lower
Range Value
Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mA Output xSettings > Upper
Range Value
The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA Output, that is, to
define the relationship between mA Output Process Variable and the mA Output signal.
LRV is the value of mA Output Source represented by an output of 4 mA. URV is the value of mA Output
Source represented by an output of 20 mA. Between LRV and URV, the mA Output is linear with the process
variable. If the process variable drops below LRV or rises above URV, the transmitter posts an output
saturation alert.
Procedure
Set LRV and URV as desired.
Enter LRV and URV in the measurement units used for mA Output Source.
Defaults: Specific to each process variable
Range: Unlimited
Note
You can set URV below LRV. For example, you can set URV to 50 and LRV to 100. If you do this, the mA
Output will be inversely proportional to the value of mA Output Source.
Tip
For best performance:
Set LRVLSL (lower sensor limit).
Set URVUSL (upper sensor limit).
Set these values so that the difference between URV and LRV is ≥ Min Span (minimum span).