Effect of mA Output Direction on an mA Output
mA Output Direction affects how the transmitter reports flow values via an mA Output. An mA Output is
affected by mA Output Direction only if mA Output Source is set to a flow variable.
The effect of mA Output Direction depends on the setting of Lower Range Value (LRV).
If Lower Range Value = 0, see Figure 8-1.
If Lower Range Value > 0, see Figure 8-1 and adapt the chart.
If Lower Range Value < 0, see Figure 8-2.
Figure 8-1: Effect of mA Output Direction on an mA Output: Lower Range Value = 0
mA Output Direction = Normal
mA output
-x 0 x
Reverse flow Forward flow
20
12
4
mA Output Direction = Absolute Value
mA output
-x 0 x
Reverse flow Forward flow
20
12
4
Lower Range Value = 0
Upper Range Value = x
Integrate the meter with the control system Configuration and Use Manual
April 2019 MMI-20048166
98 Micro Motion 4200 Transmitters