Cerabar M, Deltabar M, Deltapilot M Commissioning with the FF configuration program
Endress+Hauser 197
Flow unit/FLOW_UNIT
Entry
Index: 17
Data type: unsigned16
Access: OOS
Select flow unit.
Prerequisite:
• Deltabar M differential pressure transmitter
Make sure that the unit suits the flow mode selected. → See also ä 196, Flow
meas. type/FLOW_TYPE parameter description.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow type Flow meas. type/FLOW_TYPE.
When the flow type is changed, conversion is not possible.
Possible units for Flow meas. type/FLOW_TYPE = Volume operat. cond.:
•m
3
/s, m
3
/min, m
3
/h, m
3
/d
• l/s, l/min, l/h
• hl/s, hl/min, hl/d
•ft
3
/s, ft
3
/min, ft
3
/h, ft
3
/d
• ACFS, ACFM, ACFH, ACFD
•ozf/s, ozf/min
• gal/S, gal/min, gal/h, gal/d
• Igal/s, Igal/min, Igal/h
• bbl/s, bbl/min, bbl/h, bbl/d
Factory setting:
m³/s
Possible units for Flow meas. type/FLOW_TYPE = Volume norm. cond.:
•Nm
3
/s, Nm
3
/min, Nm
3
/h, Nm
3
/d
Factory setting:
Nm³/s
Possible units for Flow meas. type/FLOW_TYPE = Volume std. cond.:
•Sm
3
/s, Sm
3
/min, Sm
3
/h, Sm
3
/d
• SCFS, SCFM, SCFH, SCFD
Factory setting:
Sm3/s
Possible units for Flow meas. type/FLOW_TYPE = Mass p. cond.:
• g/s, kg/s, kg/min, kg/h
• t/s, t/min, t/h, t/d
•oz/s, oz/min
• lb/s, lb/min, lb/h
• ton/s, ton/min, ton/h, ton/d
Factory setting:
kg/s
Possible units for Flow meas. type/FLOW_TYPE = Flow in %:
•%
Factory setting:
%
DP_FLOW Transducer Block
Parameter Description