Commissioning with an operating menu (onsite display/FieldCare) Cerabar M, Deltabar M, Deltapilot M
82 Endress+Hauser
The measured variables %, level, volume and mass are available for this level mode
ä 123 "Unit before lin. (025)".
6 Select a level unit by means of the "Height unit (026)"
parameter, here "m" for example.
Menu path: Setup Extended Setup Level
Height unit (026)
A0031029
Abb. 35: Abgleich mit Referenzdruck –
Nassabgleich
A Siehe Tabelle, Schritt 8.
B Siehe Tabelle, Schritt 9.
C Siehe Tabelle, Schritt 10.
7 Select the "Wet" option by means of the "Calibration
mode (027)" parameter.
Menu path: Setup Extended Setup Level
Calibration mode (027)
8 If calibration is performed with a medium other than
the process medium, enter the density of the
calibration medium in the "Adjust density (034)"
parameter, here 1 g/cm
3
(1 SGU) for example.
Menu path: Setup Extended Setup Level
Adjust density (034)
9 The pressure for the lower calibration point is
present at the device, here 0.5 m covered / 49 mbar
(0.71 psi) for example.
Enter the volume value for the lower calibration
point via the "Empty calib. (028)" parameter, here 0
liters for example. (The pressure currently measured
is displayed as the height, here 0.5 m (1.6 ft) for
example.)
Menu path: Setup Extended Setup Level
Empty calib. (028)
10 The pressure for the upper calibration point is
present at the device, here 4.5 m covered / 441 mbar
(6.4 psi) for example.
Enter the volume value for the upper calibration
point via the "Full calib. (031)" parameter, here
"1000 liters" (264 gal) for example. The pressure
currently measured is displayed as the height, here
"4.5 m" (14.8 ft) for example.
Menu path: Setup Extended Setup Level Full
calib. (031)
11 If calibration was performed with a medium other
than the process medium, specify the density of the
process medium in the "Process density (035)"
parameter.
Menu path: Setup Extended Setup Level
Process density (035)
12 Result:
The measuring range is set for 0 to 1000 l (264 gal).
Description
h
p
g
=
×r
h
p
g
=
×r
r=1
g
cm
3
V
[l]
h
[m]
h
[m]
p
[mbar]