Cerabar M, Deltabar M, Deltapilot M Commissioning with an operating menu (onsite display/FieldCare)
Endress+Hauser 87
Error message F510 "Linearization" and alarm current appears as long as the table is being
entered and until the table is activated.
4 To enter another point in the table, select the "Next
point" option via the "Edit table (042)" parameter.
Enter the next point as explained in Step 3.
Menu path: Setup Extended Setup
Linearization Edit table (042)
5 Once all the points have been entered in the table,
select the "Activate table" option via the "Lin. mode"
parameter.Lin. mode (037)
Menu path: Setup Extended Setup
Linearization Lin. mode (037)
6 Result:
The measured value after linearization is displayed.