3.4 Resource block
The resource block contains the parameters used to describe physical resources of
the device. It has no linkable inputs or outputs. It is opened by a click on the
resource line.
—E+H_CERABAR_S_XXXXXXXX
—RESOURCE_XXXXXXXX (RB)
—TRANSDUCER_XXXXXXXX (TBPR)
—ANALOG_INPUT_XXXXXXXX (AI)
If the NI-FBUS Configurator is being used, a series of file tabs appears on the screen.
The files can be opened to view and/or edit the parameters in the following table. A
short description of the parameter function appears on the side of the screen. A
change in the parameter is stored by pressing the WRITE CHANGES button when the
block is out of service. Press the READ ALL button to check the values stored in the
device. The following are of particular interest.
The function of the resource block parameters not described here can can be taken
from the Foundation Fieldbus specification, see
"http://www.fieldbus.org"
.
Parameter Description
TAG_DESC
User description of the intended application of the block.
MODE_BLK
Lists the actual, target, permitted and normal operating modes of the
block.
Target: changes the operating mode of the block
Actual: indicates the current operating mode of the block
Permitted: states which operating modes are allowed
Normal: indicates the normal operating mode of the block
The possible operating modes of the resources block are:
AUTO: the block is operating as normal
OOS: the block is out of service.
If the resource block is out of service, then all blocks within the device
(resource) are forced into the same status.
RS_STATE
Indicates the state of the resource block application state machine
On-line: block in AUTO mode
Standby: block in OOS mode
WRITE_LOCK
Indicates the status of DIP-switch WP.
RESTART
Allows a manual restart:
UNINITIALISED: no status
RUN: normal operational status
RESOURCE: resets the resource block parameters
DEFAULTS: Resets all Foundation Fieldbus parameters within the device,
but not the manufacturer specific parameters.
PROCESSOR: make a warm start of the processor
BLOCK_ERROR
Shows error status of software and hardware components
Out-of-Service: the block is in OOS mode
Simulation active: shows the setting of DIP-switch WP
BLOCK_ALM
Shows any configuration, hardware, connection and system problems in
the block. The cause of the alert is to be seen in the subcode field.
Cerabar S FF 3 Foundation Fieldbus Interface
Endress+Hauser 19