EasyManua.ls Logo

Endress+Hauser Cerabar S Series - Calibration Methods

Endress+Hauser Cerabar S Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.2 Calibration via a configuration tool
The basic calibration and other functions can be set using a configuration tool. See
Chapter 5 for pressure measurement and Chapter 6 for level measurement. The
majority of the parameters are to be found as manufacturer’s parameters in the
transducer block, see Chapter 4.5. The scaling of the analog input block, Chapter 3.6,
is also to be found in Chapter 5.6 or 6.7.
Procedure1) Integrate the device into the configuration tool before calibrating, see Chapter 3.2.
2) Select the transducer block to perform the calibration, select the analog input block
for the scaling.
3) Set the MODE_BLK parameter to “Out of Service” before proceeding.
4) Download the edited parameter before proceding with the next step.
5) Switch the MODE_BLK to “Auto” when the calibration is complete.
Note!
For the NI-FBUS configurator, the transducer block parameters are to be found in the
“Others” folder, the analog input block parameters in the “Scaling” folder.
Note!
Cerabar S FF 4 Operation
Endress+Hauser 31

Related product manuals