3.9 Checklist for commissioning
1. Configure the network and integrate the device.
− Identify the device by means of the device ID and serial number.
− If appropriate, assign a new PD_TAG, see page 17.
2. Configure the resource block, see Chapter 3.4.
− Check the position of the hardware switch in WRITE_LOCK:
− If "locked" is displayed, change the position of the DIP-switch, see Chapter 3.2.
− If appropriate, change the block tag (right-hand click on tree).
− Set MODE_BLK_TARGET to Out-of-Service.
− Reset the device to factory values by using the function RESTART => Defaults
(this function may also be available with a right-hand click on the device name).
− If appropriate, assign a tag description (TAG_DESC).
− Set MODE_BLK_TARGET to Auto.
3. Configure the transducer block, see Chapters 3.5, 5 and 6.
− If appropriate, change the block tag (right-hand click on tree).
− Set MODE_BLK_TARGET to Out-of-Service.
− If appropriate, assign a tag description (TAG_DESC).
− Configure the device as described in Chapters 5 or 6 (via configuration tool).
− Set MODE_BLK_TARGET to Auto.
4. Configure the analog input block, see Chapters 5.6 and 6.7.
− If appropriate, change the block tag (right-hand click on tree).
− Set MODE_BLK_TARGET to Out-of-Service.
− If appropriate, assign a tag description (TAG_DESC).
− Set Channel to 1.
− Set L_TYPE to "DIRECT" if the OUT value is to be in technical units e.g. bar
to "INDIRECT" if the OUT value is to be scaled, see page 24 or Chapters 5.6 or 6.7.
− Set the desired output damping in PV_TIME.
− If appropriate, set the advisory and critical alarms.
− Set MODE_BLK_TARGET to Auto.
5. Link the function blocks in the function block editor.
6. If appropriate, check the configuration by using the SIMULATE function,
see also Chapter 8.2.
7. Download the configuration (right-hand click on device name).