Deltabar S
Endress+Hauser 13
PMD 70, FMD 76 (with ceramic measuring diaphragms)
Explanation of terms
Nominal
value
Measurement limit Span MWP
1
Overload
2
Min.
operating
pressure
3
Versions in the
order code
4
lower (LRL) upper (URL) recom-
mended
min./max.
minimum
5
on one side on both
sides
inH
2
O
[mbar]
inH
2
O [mbar] inH
2
O
[mbar]
inH
2
O [mbar] inH
2
O [mbar] psi [bar] psi [bar] psi [bar] psi [mbar
abs
]
10 (25) -10 (25) +10 (+25) 10 (25) 0.1 (0.25) 145 (10) 145 (10) 217 (15) 14 (1) 7B
40 (100) -40 (-100) +40 (+100) 10/40 (25/100) 0.4 (1) 232 (16) 232 (16) 348 (24) 14 (1) 7D
200 (500) -200 (-500) +200 (+500) 13/200 (33/500) 2 (5) 1450 (100) 1450 (100) 2175 (150) 14 (1) 7F
1200 (3000) -1200 (-3000) +1200
(+3000)
80/1200
(200/3000)
12 (30) 1450 (100) 1450 (100) 2175 (150) 14 (1) 7H
1) MWP = Maximum working pressure. → See also page 26, section "Pressure specifications".
2) The specified overload only applies to the measuring cell. The maximum pressure for the measuring device is dependent on the weakest element,
with regard to pressure, of the selected components. → See also page 26, section "Pressure specifications".
3) Min. operating pressure at the reference operating conditions for silicone oil. Min. operating pressure at 185°F (85°C): to 0.145 psi
abs
(10 mbar abs)
4) Versions in the order code → See also page 53 ff, feature 40 "Measuring cell, nominal operating range, PN"
5) Minimum span that can be calibrated, turn down > 100:1 on request
P01-xxxxxxxx-05-xx-xx-xx-001
Example: 200 inH
2
O (500 mbar) sensor
1Set span
2Nominal value
i
Upper range limit (URL)
3 Nominal measuring range
LRL Lower range limit
URL Upper range limit
LRV Lower range value
URV Upper range value
Explanation of the term 'Turn down (TD)'
(TD = turn down)
Turn down = nominal value/set span
Example:
Nominal value = 200 inH
2
O (500 mbar)
Set span = 40 inH
2
O (100 mbar)
TD = 5:1
–500 mbar
(-200 inH O)
2
+ 500 mbar
(+200 inH O)
2
0
1
2
3
100
(40 inH O)
2
LRL
LRV
URL
URV