Deltabar S
Endress+Hauser 15
Damping Via display module, handheld terminal or PC with operating program, continuous from 0...999 s
Additionally for HART: via DIP-switch on the electronic insert, switch position "On = set value" and "Off"
Factory setting: 2 s
Power supply
Electrical connection Note!
When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions (XAs) or Installation or Control Drawings
(ZDs). See also page 67, section "Safety Instructions" and "Installation/Control Drawings".
Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
4 to 20 mA HART
P01-xMx7xxxx-04-xx-xx-xx-001
Electrical connection 4 to 20 mA HART
1Housing
2 Jumper for 4 to 20 mA test signal.
See also page 16, section "Measuring 4 to 20 mA" .
3 Internal ground terminal
4 External ground terminal
5 4 to 20 mA test signal between positive and test terminal
6 Minimum supply voltage = 10.5 V DC, jumper is inserted in accordance with the illustration.
7 Minimum supply voltage = 11.5 V DC, jumper is inserted in "Test" position.
PROFIBUS PA
The two-wire cable must be connected to the "PA+" and "PA–" terminals.
Foundation Fieldbus
The two-wire cable must be connected to the "FF+" and "FF–" terminals.
4 to 20mA
Test
4to20mA
10.5 V DC
11.5 V DC
4... 20mA
Test
Test
Test
1
2
3
4
5
6
7