Deltabar S
Endress+Hauser 15
Damping • Via display module, handheld terminal or PC with operating program, continuous from 0...999 s
• Additionally for HART: via DIP-switch on the electronic insert, switch position "On = set value" and "Off"
• Factory setting: 2 s
Power supply
Electrical connection Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions (XAs) or Installation or Control Drawings
(ZDs). → See also page 67, section "Safety Instructions" and "Installation/Control Drawings".
• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
4 to 20 mA HART
P01-xMx7xxxx-04-xx-xx-xx-001
Electrical connection 4 to 20 mA HART
1Housing
2 Jumper for 4 to 20 mA test signal.
→ See also page 16, section "Measuring 4 to 20 mA" .
3 Internal ground terminal
4 External ground terminal
5 4 to 20 mA test signal between positive and test terminal
6 Minimum supply voltage = 10.5 V DC, jumper is inserted in accordance with the illustration.
7 Minimum supply voltage = 11.5 V DC, jumper is inserted in "Test" position.
PROFIBUS PA
The two-wire cable must be connected to the "PA+" and "PA–" terminals.
Foundation Fieldbus
The two-wire cable must be connected to the "FF+" and "FF–" terminals.
4 to 20mA
Test
4to20mA
10.5 V DC
11.5 V DC
4... 20mA
Test
Test
Test
1
2
3
4
5
6
7