Deltabar S
26 Endress+Hauser
Pressure specifications The maximum pressure for the measuring device is dependent on the lowest-rated element with regard to
pressure, see the following sections for this:
page 12, section "Measuring range"
page 23, section "Oxygen applications"
chapter "Mechanical construction".
Observe pressure-temperature dependency.
Note!
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference
temperature of 68°F (20°C) or 100°F for ANSI flanges.
Test pressure (Over pressure limit OPL) = MWP (nameplate) x 1.5.
The pressure values permitted at higher temperatures can be found in the following standards:
EN 1092-1: 2001 Tab. 18
ASME B 16.5a – 1998 Tab. 2-2.2 F316
ASME B 16.5a – 1998 Tab. 2.3.8 N10276
JIS B2201
Mechanical construction
Housing dimensions, optional
display on the side (T14)
P01-xMD7xxxx-06-00-xx-xx-000
Front view, left-hand side view, top view
Housing dimensions, optional
display on the top (T15)
P01-xMD7xxxx-06-00-xx-xx-001
Front view, left-hand side view, top view
FIELD TERMINALS
4.37”
(111)
4.37”
(111)
5.98”
(152)
5.71”
(145)
4.53”
(115)
6.06”
(154)
6.50”
(165)
5.00”
(127)
6.10”
(155)