Deltabar S
50 Endress+Hauser
P01-xxxxxxxx-05-xx-xx-xx-006
Presentation of the response time (T90%)
1 Pressure step
2Output signal
Installation instructions Instructions for diaphragm seal systems
The diaphragm seal together with the transmitter form a closed, calibrated system, which is filled through
ports in the diaphragm seal and in the measuring system of the transmitter. These ports are sealed and must
not be opened.
When selecting the measuring cell, observe the zero shift resulting from the hydrostatic pressure of the filling
fluid columns in the capillaries. ( See the following illustration).
When using a mounting bracket, sufficient strain relief must be allowed in order to prevent the capillary from
exceeding a bending radius 4" / 100 mm.
The temperature and length of both capillaries should be the same when using two-sided diaphragm seal
systems.
90 %
100 %
t
1
2
T90%
Minimise response time by Comments
Larger capillary internal diameter The temperature effect increases with increasing diameter.
Shorter capillaries
Filling oil with lower viscosity Observe compatibility of the filling oil with the fluid.
Observe the filling oil operating limits.
Selecting the measuring cell (observe the hydrostatic pressure of the filling fluid column in the
capillaries!)
P01-FMD78xxx-11-xx-xx-xx-004.eps
+
+
max.
min.
DH=1m
Hu = 0.2 m
Hv = 1.8 m
H1 = 0.3 m
= 1.0 kg/dmr
M
3
p
i
= 0.96 kg/dmr
Fl
3
Tank with water
Capillaries with silicone oil