Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
102 Endress+Hauser
FSAFE TYPE/
FSAFE_TYPE
Selection
Index: 37
Data type: unsigned8
Access: man, OOS
If the Analog Input Block receives an input value or simulation value with the status BAD,
the Analog Input Block continues working with the failsafe mode defined by means of this
parameter.
The following options are available by means of the FSAFE TYPE/FSAFE TYPE parameter:
Last Good Value
The last valid value is used for further processing with the status UNCERTAIN.
Fail Safe Value
The value specified by means of the FSAFE_VALUE/FSAFE_VALUE parameter is used for
further processing with the status
UNCERTAIN. See this Table, FSAFE TYPE/FSAFE TYPE parameter description.
•Wrong Value
The current value is used for further processing with the status BAD.
!
Note!
The failsafe mode is also activated if the "Out of service" option was selected by means of the
Block Mode/MODE_BLK parameter, "Target" element.
Factory setting:
Fail Safe Value
FSAFE_VALUE/
FSAFE_VALUE
Entry
Index: 38
Data type: float
Access: OOS
Enter the value for the "Fail Safe Value" option selected by means of the FSAFE TYPE/FSAFE
TYPE parameter.
See also this Table, FSAFE TYPE/FSAFE TYPE parameter description.
Factory setting:
0
High High Alarm Output
Discrete/
HIHI_ALM_OUT_D
Index: 39
Data type: DS66
Access: auto, OOS, man
Digital outputs (1 or 0) for limit value monitoring. If "Process Value/PV High High Limit/
HI_HI_LIM", the output is set to "1".
High Alarm Output Dis-
crete/HI_ALM_OUT_D
Index: 40
Data type: DS66
Access: auto, OOS, man
Digital outputs (1 or 0) for limit value monitoring. If "Process Value/PV High Limit/
HI_LIM", the output is set to "1".
Low Alarm Output Dis-
crete/LO_ALM_OUT_D
Index: 41
Data type: DS66
Access: auto, OOS, man
Digital outputs (1 or 0) for limit value monitoring. If "Process Value/PV Low Low Limit/
LO_LO_LIM", the output is set to "1".
Low Low Alarm Output
Discrete/LOLO_ALM_
OUT_D
Index: 42
Data type: DS66
Access: auto, OOS, man
Digital outputs (1 or 0) for limit value monitoring. If "Process Value/PV Low Limit/
LO_LIM", the output is set to "1".
Select Alarm Mode/
ALARM_MODE
Index: 43
Data type: DS66
Access: auto, OOS, man
Facilitates alarm mode settings for the Alarm Output Discrete/ALM_OUT_D parameter
Options:
Low Cutoff/LOW_CUT
HiHi or LoLo Alarm activates ALARM_OUT_D/HIHI_LOLO
Hi or Lo Alarm activates ALARM_OUT_D/HI_LO
Analog Input Block
Parameter Description

Table of Contents