Level measurement (via local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
106 Endress+Hauser
9.2 "Level easy pressure" level selection
9.2.1 Calibration with reference pressure – wet calibration
Example:
In this example, the level in a tank should be measured in m. The maximum level is 3 m (9.8 ft).
The pressure range is set to 0-300 mbar (4.5 psi).
Prerequisite:
The measured variable is in direct proportion to the pressure.
The tank can be filled and emptied.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
The values entered for EMPTY CALIB. and FULL CALIB. must be at least 1% apart for the "Level
easy pressure" level mode. The value will be rejected with a warning message if the values are too
close together. Further limit values are not checked; i.e. the values entered must be appropriate
for the sensor and the measuring task so that the measuring device can measure correctly.
For a description of the parameters mentioned, see
ä 134, Table 2: GROUP SELECTION MEASURING MODE
ä 142, Table 6: OPERATING MENU SETTINGS POSITION ADJUSTMENT
ä 146, Table 8: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level easy pressure".
For a description of further relevant parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMP75xxx-19-xx-xx-xx-008
Fig. 19: Calibration with reference pressure –
wet calibration
1 See Table, Step 9.
2 See Table, Step 10.
2 Carry out position adjustment if necessary. ä 142,
Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
3 Select the "Level" measuring mode via the MEASURING
MODE parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE
4 If necessary, select the "Level easy pressure" level mode
using the LEVEL SELECTION parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE "Level" LEVEL SELECTION
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE "Level"
LEVEL SELECTION
0 mbar
300 mbar
3 m
0 m

Table of Contents

Other manuals for Endress+Hauser Deltabar S PMD75

Related product manuals