Level measurement (via local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
110 Endress+Hauser
9.3 "Level easy height" level selection
9.3.1 Calibration with reference pressure – wet calibration
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of
1000 liters (264 US gal) corresponds to a level of 4.5 m (15 ft). The minimum volume of 0 liters
corresponds to a level of 0.5 m (1.6 ft) since the device is mounted below the level lower-range
value. The density of the fluid is 1 kg/dm
3
.
Prerequisite:
The measured variable is in direct proportion to the pressure.
The tank can be filled and emptied.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
The values entered for EMPTY CALIB./FULL CALIB., EMPTY PRESSURE/FULL PRESSURE and
EMPTY HEIGHT/FULL HEIGHT must be at least 1% apart for the "Level easy height" level mode.
The value will be rejected with a message if the values are too close together. Further limit values
are not checked; i.e. the values entered must be appropriate for the sensor and the measuring task
so that the measuring device can measure correctly.
For a description of the parameters mentioned, see
ä 134, Table 2: GROUP SELECTION MEASURING MODE
ä 142, Table 6: OPERATING MENU SETTINGS POSITION ADJUSTMENT
ä 150, Table 9: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level easy height".
For a description of further relevant parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMC71xxx-19-xx-xx-xx-009
Fig. 23: Calibration with reference pressure –
wet calibration
1 See Table, Steps 10 and 11.
2 See Table, Step 12.
3 See Table, Step 13.
2 Carry out position adjustment if necessary. ä 142,
Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
3 Select the "Level" measuring mode via the MEASURING
MODE parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE
1000 l
0.5 m
4.5 m
0l
r =1
kg
dm
3