Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 93
7.4 Analog Input Block (function block)
Enter Reset Code/
ENTER_RESET_CODE
Entry
Index: 32
Data type: unsigned16
Access: auto, OOS
Reset parameters completely or partially to factory values or delivery status.
→ See also Operating Instructions BA00301P (Deltabar S) or BA00302P (Cerabar S) or
BA00372P (Deltapilot S), "Factory setting" (reset) section.
Factory setting:
0
Operating Hours/
OPERATING_HOURS
Display
Index: 33
Data type: Unsigned32
Access: read only
Displays the hours of operation. This parameter cannot be reset.
Status History/
STATUS_HISTORY
Display
Index: 34
Data type: visible string
Access: read only
This parameter displays pending alarms and warnings in hexadecimal numerical format
(max. 18). Each message is assigned to a bit in the order of the error code in accordance with
Section 12.1 "Messages".
Analog Input Block
Parameter Description
Static Revision/ST_REV
Display
Index: 1
Data type: usigned16
Access: read only
Displays the counter for static parameters of the Analog Input Block.
The counter is incremented by one with each change of a static parameter of the Analog
Input Block. The counter counts up to 65535 and then starts again at zero.
Tag Description/
TAG_DESC
Entry
Index: 2
Data type: octet string
Access: auto, OOS
Enter a description for the related block or the measuring point e.g. TAG number (max.
32 alphanumeric characters).
Strategy/STRATEGY
Entry
Index: 3
Data type: unsigned16
Access: auto, man, OOS
Enter user-specific value for grouping and thus faster evaluation of the blocks.
Grouping takes place by entering the same numerical value for the Strategy/STRATEGY
parameter of the block in question.
Input range:
0 to 65535
Factory setting:
0
Alert Key/ALERT_KEY
Entry
Index: 4
Data type: unsigned8
Access: auto, man, OOS
Enter the identification number for the measuring device or for each individual block.
The control level uses this identification number to sort alarm and event messages and
initiate other processing steps.
Input range:
1 to 255
Factory setting:
0
Diagnostic Transducer Block
Parameter Description