EasyManua.ls Logo

Endress+Hauser Deltabar S PMD75 - Level Standard Level Selection; Pressure Linearized Level Mode

Endress+Hauser Deltabar S PMD75
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (FF configuration program)
Endress+Hauser 27
5.5 "Level standard" level selection,
"Pressure linearized" level mode
5.5.1 Semiautomatic entry of the linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
The tank can be filled. The linearization characteristic must rise continuously.
A minimum gap of 0.5 % of the distance between two points must be maintained. Spans for the
"Pressure linearized" option: HYDR. PRESS MAX. – HYDR. PRESS MIN.; TANK CONTENT
MAX. – TANK CONTENT MIN. Spans for the "Height linearized" option: LEVEL MAX – LEVEL
MIN; TANK CONTENT MAX. – TANK CONTENT MIN.
!
Note!
See also Operating Instructions BA00301P for Deltabar S or Operating Instructions BA00302P for
Cerabar S or Operating Instructions BA00372P for Deltapilot S, "Level measurement" section.
For a description of the parameters mentioned, see
ä 53, Pressure Transducer Block.
ä 93, Analog Input Block
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMP75xxx-19-xx-xx-xx-002
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 The following options are available for performing
position adjustment:
By means of the parameters
Pos.Zero Adjust/ ZERO_POSITION_ADJUST
( ä 59) or
Pos. Input Value/POSITION_INPUT_VALUE
( ä 59) or
Calib. Offset/CALIBRATION_OFFSET ( ä 59).
Carry out basic setup:
4 Select the measuring mode if necessary:
Select the "Level linearized" option by means of the
Linearization/LINEARIZATION parameter.
By means of the Primary Value Type/
PRIMARY_VALUE_TYPE parameter, select the
"Volume" option. See also Point 3 in the following
note.
5 Select the "LEVEL standard" option by means of the
Level Selection/LEVEL_SELECTION parameter.
6 Select a pressure unit via the Calibration Units/
CAL_UNIT parameter, here mbar for example.
7 By means of the Level Mode/LEVEL_MODE parameter,
select the "Pressure linearized" option.
8 By means of the Lin. Measurand/LINEAR_
MEASURAND parameter, select the "Pressure and
volume" option.
9 Select a volume unit via the Unit Volume/
VOLUME_UNIT parameter, here m
3
for example.
3.5
0
0 350
V
[m ]
3
p
[mbar]

Table of Contents

Other manuals for Endress+Hauser Deltabar S PMD75

Related product manuals