Level measurement (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
26 Endress+Hauser
!
Note!
1. For this level mode, the measured variables %, level, volume and mass are available.
→ ä 61 ff.
2. You can also specify customer-specific units. See parameter description for Calibration Units/
CAL_UNIT (→ ä 54), Height Unit/HEIGHT_UNIT (→ ä 62), Unit Volume/
VOLUME_UNIT (→ ä 64) and Mass Unit/MASS_UNIT (→ ä 65).
11 By means of the Adjust Density/ADJUST_DENSITY
and Density Unit/DENSITY_UNIT parameters, enter a
value for the density, here 1 kg/dm
3
for example.
12 Enter the tank volume via the Tank Volume/
TANK_VOLUME parameter, here 5 m
3
for example.
13 Enter the tank height via the Tank Height/
TANK_HEIGHT parameter, here 4 m (13 ft) for
example.
14 By means of the Zero Point/ZERO_POSITION
parameter, enter the level offset, here –0.5 m (-1,6 ft) for
example.
15 Set the Pressure Transducer Block to the "Auto" block
mode.
16 Where necessary, configure the Channel/CHANNEL
(→ ä 96), Linearization Type/L_TYPE (→ ä 97),
Transducer Scale/XD_SCALE (→ ä 95) and Output
Scale/OUT_SCALE (→ ä 96) parameters by means of
the Analog Input Block.
17 Result:
The device is ready for level measurement.
Description