EasyManua.ls Logo

Endress+Hauser Deltabar S PMD75 - Height Linearized Level Mode

Endress+Hauser Deltabar S PMD75
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Level measurement (via local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
124 Endress+Hauser
9.6 "Height linearized" level mode
9.6.1 Wet calibration and semiautomatic entry of the linearization
table
Example:
In this example, the height and the volume should be measured at the same time.
Prerequisite:
The tank can be filled. The linearization characteristic must rise continuously.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P), Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
For a description of the parameters mentioned, see
ä 142, Table 6: OPERATING MENU SETTINGS POSITION ADJUSTMENT
ä 155, Table 10: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level standard"
ä 170, Table 13: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
MODE "Height linearized"
ä 186, Table 18: GROUP SELECTION OPERATING MENU SETTINGS
LINEARIZATION – Local operation
ä 189, Table 19: MANUFACTURER VIEW OPERATING MENU SETTINGS
LINEARIZATION – FieldCare
For a description of further parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMP75xxx-19-xx-xx-xx-004
2 Carry out position adjustment if necessary. ä 142,
Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
Perform calibration for the 1st measured variable:
3 Select the "Level" measuring mode via the MEASURING
MODE parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE
4 If necessary, select the "Level standard" level mode using
the LEVEL SELECTION parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE "Level" LEVEL SELECTION
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE "Level"
LEVEL SELECTION

Table of Contents

Other manuals for Endress+Hauser Deltabar S PMD75

Related product manuals