Table 13: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Height linearized"
Parameter name Description
The following parameters are displayed if you selected the "Height linearized" option for the LEVEL MODE parameter.
Select this level mode if you require two measured variables or if the container shape is given with value pairs, e.g. height
and volume.
The following combinations are possible:
• Height + volume
• Height + mass
• Height + %
• %-height + volume
• %-height + mass
• %-height + %
The 1st measured variable (%-height or height) must be in direct proportion to the measured pressure. The 2nd measured
variable (volume, mass or %) must not be in direct proportion. A linearization table has to be entered for the 2nd
measured variable. The 2nd measured variable is assigned to the 1st measured variable by means of this table.
Prerequisite:
• MEASURING MODE = Level
• LEVEL MODE = Height linearized (→ ä 156).
Note:
See also
– → ä 155 ff, Table 10: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL SELECTION "Level
standard" – general
– → ä 183 ff, Table 16: OPERATING MENU → SETTINGS → EXTENDED SETUP "Level"
– → ä 186 ff, Table 18: GROUP SELECTION → OPERATING MENU → SETTINGS → LINEARIZATION – Local
operation and Table 19: MANUFACTURER VIEW → OPERATING MENU → SETTINGS → LINEARIZATION –
FieldCare
– → ä 201 ff, Table 28: OPERATING MENU → PROCESSINFO → PROCESS VALUES "Level"
– → ä 105 ff, Section 9 "Level measurement (via local operation and FieldCare)".
COMB. MEASURAND (806)
Selection
Select the measured variable.
Options:
• Height and volume
• Height and mass
• Height and %
• %-height and volume
• %-height and mass
• %-height and %
Factory setting:
%-height and %
HEIGHT UNIT (708)
Selection
Select the level unit for the 1st measured variable.
Prerequisite:
• COMB. MEASURAND = Height and volume, height and mass or height and %
Options:
•mm
•dm
•cm
•m
•inch
•ft
•User unit, → see also the following parameter descriptions for CUSTOMER UNIT H
and CUST. UNIT. FACT. H.
Factory setting:
m