Level measurement (via local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
118 Endress+Hauser
9.5 "Level standard" level selection,
"Pressure linearized" level mode
9.5.1 Semiautomatic entry of the linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
The tank can be filled. The linearization characteristic must rise continuously.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
For a description of the parameters mentioned, see
ä 134, Table 2: GROUP SELECTION MEASURING MODE
ä 142, Table 6: OPERATING MENU SETTINGS POSITION ADJUSTMENT
ä 155, Table 10: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level standard"
ä 158, Table 11: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
MODE "Linear"
ä 186, Table 18: GROUP SELECTION OPERATING MENU SETTINGS
LINEARIZATION – Local operation
ä 189, Table 19: MANUFACTURER VIEW OPERATING MENU SETTINGS
LINEARIZATION – FieldCare
For a description of further relevant parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMP75xxx-19-xx-xx-xx-002
2 Carry out position adjustment if necessary. ä 138,
Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
Carry out basic setup:
3 Select the "Level" measuring mode via the MEASURING
MODE parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE
4 If necessary, select the "Level standard" level mode using
the LEVEL SELECTION parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE "Level" LEVEL SELECTION
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE "Level"
LEVEL SELECTION
3.5
0
0 350
V
[m ]
3
p
[mbar]