Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (via local operation and FieldCare)
Endress+Hauser 117
!
Note!
1. For this level mode, the measured variables %, level, volume and mass are available. ä 158
ff.
2. You can also specify customer-specific units. See parameter descriptions for PRESS. ENG.
UNIT (060) ( ä 155), HEIGHT UNIT (708) ( ä 158), UNIT VOLUME (313) ( ä 159)
and MASS UNIT (709) ( ä 160).
2 If necessary, select the "Level standard" level mode using
the LEVEL SELECTION parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE "Level" LEVEL SELECTION
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE "Level"
LEVEL SELECTION
3 Local operation:
Select the BASIC SETUP function group. Menu path:
GROUP SELECTION OPERATING MENU
SETTINGS BASIC SETUP
4 Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
5 Select the "Linear" option by means of the LEVEL MODE
parameter.
6 Select the "Volume" option by means of the LIN.
MEASURAND parameter.
7 Select a volume unit via the UNIT VOLUME parameter,
here m
3
for example.
8 Select the "Dry" option by means of the CALIBRATION
MODE parameter.
9 Enter the value for density via the ADJUST DENSITY
parameter, here 1 kg/dm
3
for example.
10 Enter the tank volume via the TANK VOLUME
parameter, here 5 m
3
for example.
11 Enter the tank height via the TANK HEIGHT parameter,
here 4 m (13 ft) for example.
12 Enter the level offset via the ZERO POSITION
parameter, here –0.5 m (-1.6 ft) for example.
13 Result:
The device is ready for level measurement