Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 159
CUST. UNIT FACT. H (705)
Entry
Enter the conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
See also CUSTOMER UNIT H.
Prerequisite:
LIN. MEASURAND = Level, HEIGHT UNIT = User unit
Example:
You want the measured value to be displayed in "PU" (PU: packing unit).
MEASURED VALUE = 0.5 m (1.6 ft) i 1 PU
Entry CUSTOMER UNIT H: PU
Entry CUST. UNIT FACT. H: 2
Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
UNIT VOLUME (313)
Selection
Select the volume unit.
Prerequisite:
LIN. MEASURAND = Volume
Options:
•l
•hl
•cm
3
•dm
3
•m
3
•m
3
E
3
•ft
•ft
3
E
3
•gal
•Igal
•bbl
•User unit, see also the following parameter descriptions for CUSTOMER UNIT V
and CUST. UNIT. FACT. V
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
3
CUSTOMER UNIT V (608)
Entry
Enter text (unit) for customer-specific volume unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT. FACT. V
Prerequisite:
LIN. MEASURAND = Volume, UNIT VOLUME = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
Table 11: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Linear"
Parameter name Description