Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
134 Endress+Hauser
P01-xxxxxxxx-19-xx-xx-en-135
Fig. 36: "Level" measuring mode, LEVEL SELECTION parameter
1
2
1
1
2
1
LEVEL SELECTION
LevelStandard
LevelEasy Pressure
LevelEasyHeight
FlowPressure
Level
LevelStandard
LevelEasy Pressure
LevelEasyHeight
LEVEL SELECTION
FlowPressure Level
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE MEASUR ING MODE
QUICK SETUP
MEASURING MODE
1) Displayvia on-site display only
2) Displayvia digital communication
Table 2: GROUP SELECTION → MEASURING MODE
Parameter name Description
MEASURING MODE (389)
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
• When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
• The MEASURING MODE parameter is displayed in FieldCare in the QUICK SETUP
menus and in the BASIC SETUP function group (OPERATING MENU → SETTINGS
→ BASIC SETUP).
Options:
• Pressure
• Level
•Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level