EasyManua.ls Logo

Endress+Hauser Deltabar S PMD75 - Page 138

Endress+Hauser Deltabar S PMD75
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
138 Endress+Hauser
P01-xMx7xxxx-19-xx-xx-en-001
Fig. 38: Quick Setup menu for the "Level" measuring mode
1, 2
3
POS.INPUT VALUE
Cerabar S Absolut
pressure sensors
Deltabar S,
Cerabar S –Gauge
pressure sensors
1) LEVEL MODE ="Linear"
and CALIBRATION MODE ="dry"
3) LEVEL MODE ="LInear"
or "Height Linearized" and
CALIBRATION MODE ="wet"
POS. ZERO ADJUST
EMPTY CALIB.
FULL CALIB.
DAMPING VALUE
Pressure Level
MEASURED VALUE
QUICK SETUP
MEASURING MODE
2) LEVEL MODE ="Pressure Linearized"
Flow
Table 4: QUICK SETUP "Level"
Parameter name Description
This menu displays the most important parameters for the "Level" measuring mode.
Prerequisite:
MEASURING MODE = Level
Note:
See also
ä 155 ff, Table 10: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL SELECTION "Level
standard" to Table 13: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Height
linearized"
ä 183 ff, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 186 ff, Table 18: GROUP SELECTION OPERATING MENU SETTINGS LINEARIZATION – Local
operation and Table 19: MANUFACTURER VIEW OPERATING MENU SETTINGS LINEARIZATION –
FieldCare
ä 201 ff, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level"
ä 105 ff, Section 9 "Level measurement (via local operation and FieldCare)".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The digital output
value of the Analog Input Block OUT no longer displays the same value as the local
operation or the MEASURED VALUE. The device has to be recalibrated if the measuring
mode is changed. ä 105 ff, Section 9 "Level measurement (via local operation and
FieldCare)".
Options:
Pressure
Level
•Deltabar S: Flow
Factory setting:
Cerabar S and Deltabar S: Pressure
Deltapilot S: Level
LEVEL SELECTION (020)
Selection
Select the level mode.
Parameter description, ä 135.
Factory setting:
Level easy pressure

Table of Contents