Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 171
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT. FACT. H.
Prerequisite:
• COMB. MEASURAND = Height and volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and mass, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter the conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
→ See also CUSTOMER UNIT H.
Prerequisite:
• COMB. MEASURAND = Height and volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and mass, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m i 1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
UNIT VOLUME (313)
Selection
Select the volume unit for the 2nd measured value.
Prerequisite:
• COMB. MEASURAND = Height and volume or %-height and volume
Options:
•l
•hl
•cm
3
•dm
3
•m
3
•m
3
E
3
•ft
•ft
3
E
3
•gal
•Igal
•bbl
•User unit, → see also the following parameter descriptions for CUSTOMER UNIT V
and CUST. UNIT. FACT. V
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
→ See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
3
Table 13: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Height linearized"
Parameter name Description