EasyManua.ls Logo

Endress+Hauser Deltabar S PMD75 - Page 171

Endress+Hauser Deltabar S PMD75
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 171
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here. See also CUST.
UNIT. FACT. H.
Prerequisite:
COMB. MEASURAND = Height and volume, HEIGHT UNIT = User unit
COMB. MEASURAND = Height and mass, HEIGHT UNIT = User unit
COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter the conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
See also CUSTOMER UNIT H.
Prerequisite:
COMB. MEASURAND = Height and volume, HEIGHT UNIT = User unit
COMB. MEASURAND = Height and mass, HEIGHT UNIT = User unit
COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
Example:
You want the measured value to be displayed in "PU" (PU: packing unit).
MEASURED VALUE = 0.5 m i 1 PU
Entry CUSTOMER UNIT H: PU
Entry CUST. UNIT FACT. H: 2
Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
UNIT VOLUME (313)
Selection
Select the volume unit for the 2nd measured value.
Prerequisite:
COMB. MEASURAND = Height and volume or %-height and volume
Options:
•l
•hl
•cm
3
•dm
3
•m
3
•m
3
E
3
•ft
•ft
3
E
3
•gal
•Igal
•bbl
•User unit, see also the following parameter descriptions for CUSTOMER UNIT V
and CUST. UNIT. FACT. V
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
3
Table 13: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Height linearized"
Parameter name Description

Table of Contents

Other manuals for Endress+Hauser Deltabar S PMD75

Related product manuals