Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
54 Endress+Hauser
Calibration Lowest Point/
CAL_POINT_LO
Entry
Index: 17
Data type: float
Access: OOS
Enter the lower point of the sensor characteristic curve in the event of sensor recalibration.
By means of this parameter, you can assign a new target pressure value to a reference
pressure present at the device.
The pressure value present and the target pressure value specified for this parameter
correspond to the lower point in the sensor characteristic curve. Position adjustment has to
be performed again for the device following sensor recalibration.
!
Note!
• The sensor recalibration can be reset via the Enter Reset Code /ENTER_RESET_CODE
parameter (→ ä 93) with the "2509" code.
• The Lo Trim Measured/LOW_TRIM_MEASURED parameter (→ ä 60) displays the
pressure value that was present at the device during calibration and was used for
calibrating the lower point of the sensor characteristic curve.
• For calibrating the upper point of the sensor characteristic curve, see the parameter
description for Calibration Highest Point/CAL_POINT_HI.
Factory setting: Low sensor limit (→ Sensor Range/SENSOR_RANGE, EU_0 element)
Calibration Minimum
Span/CAL_MIN_SPAN
Display
Index: 18
Data type: float
Access: OOS
Displays the smallest possible span.
Calibration Units/
CAL_UNIT
Entry
Index: 19
Data type: unsigned16
Access: OOS
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and displayed
with the new unit.
Options:
• mbar, bar
• mmH
2
O, mH
2
O, inH
2
O, ftH
2
O
• Pa, hPa, kPa, MPa
•psi
• mmHg, inHg
•Torr
•g/cm
2
, kg/cm
2
•lb/ft
2
•atm
•gf/cm
2
, kgf/cm
2
•User unit, → see also parameter descriptions for Customer Unit P/CUSTOMER_
UNIT_PRESSURE (→ ä 60) and Cust. Unit Fact. P/CUSTOMER_FACTOR_UNIT_
PRESS (→ ä 60).
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order specifications
Sensor Type/
SENSOR_TYPE
Selection
Index: 20
Data type: unsigned16
Access: OOS
Displays the sensor type.
Sensor Range/
SENSOR_RANGE
Display
Index: 21
Data type: DS-68
Access: read only
The Sensor Range/SENSOR_RANGE parameter is a structured parameter consisting of four
elements.
EU_100
• Displays the upper measuring limit of the sensor.
EU_0
• Displays the lower measuring limit of the sensor.
UNITS_INDEX
• Displays the unit selected.
DECIMAL
• Displays the number of decimal places.
Pressure Transducer Block
Parameter Description