Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
60 Endress+Hauser
Customer Unit P/
CUSTOMER_UNIT_
PRESSURE
Entry
Index: 41
Data type: visible string
Access: auto, OOS
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also Cust. Unit.
Fact. P/CUSTOMER_FACTOR_UNIT_PRESS
Prerequisite:
• Calibration Units/CAL_UNIT (→ ä 54) = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the customer-
specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation. The
maximum number of characters in the counter is again limited to five. For example if the
customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed. In the
FF configuration program, the slash counts as a character, i.e. "crates/m2" would be
displayed as "crates/m".
Factory setting:
_ _ _ _ _ _ _ _
Cust. Unit. Fact. P/
CUSTOMER_FACTOR_
UNIT_PRESS
Entry
Index: 42
Data type: float
Access: auto, OOS
Enter the conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa".
→ See also Customer Unit P/CUSTOMER_UNIT_PRESSURE.
Prerequisite:
• Calibration Units/CAL_UNIT (→ ä 54) = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– Primary Value/PRIMARY_VALUE =10000 Pa i 1 PU
– Enter Customer Unit P/CUSTOMER_UNIT_PRESSURE: PU
– Enter Cust. Unit. Fact. P/CUSTOMER_FACTOR_UNIT_PRESS: 0.0001
– Result: Primary Value/PRIMARY_VALUE = 1 PU
Factory setting:
1.0
Lo Trim Measured/
LOW_TRIM_MEASURE
D
Display
Index: 43
Data type: float
Access: read only
Displays the pressure that was present at the device during calibration and was used for the
calibration of the lower point of the sensor characteristic curve. → See also the parameter
description for Calibration Lowest Point/CAL_POINT_LO (→ ä 54).
Hi Trim Measured/
HIGH_TRIM_MEASURE
D
Display
Index: 44
Data type: float
Access: read only
Displays the pressure that was present at the device during calibration and was used for the
calibration of the upper point of the sensor characteristic curve. → See also the parameter
description for Calibration Highest Point/CAL_POINT_HI (→ ä 53).
Pressure Transducer Block
Parameter Description