Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
92 Endress+Hauser
Alarm Displ. Time/
ALARM_DISPLAY_TIME
Entry
Index: 25
Data type: float
Access: auto, OOS
Enter the alarm display time. Once the cause of the error is rectified, the alarm display time
starts running.
!
Note!
The following applies if Ack. Alarm Mode/ACKNOWLEDGE_ALARM_MODE = On:
If an alarm appears and the alarm display time elapses before the alarm has been
acknowledged, the message is cleared once it has been acknowledged.
See also these Operating Instructions, Section 12.3 "Confirming messages".
Input range:
0 to 999.9 s
Factory setting:
0.0 s
Press. Eng. Unit/
PRESSURE_UNIT
Display
Index: 26
Data type: unsigned16
Access: read only
Displays the pressure unit selected.
The pressure unit is selected via the Calibration Units/CAL_UNIT parameter ( ä 54) in
the Pressure Transducer Block.
Pminalarm Window/
PMIN_ALARM_
WINDOW
Entry
Index: 27
Data type: float
Access: auto, OOS
Customer-specific process monitoring – enter lower pressure limit.
You can use the Select Alarmtype/SELECT_ALARM_TYPE parameter to enter how the
device responds if the operating pressure undershoots the specified value.
See also these Operating Instructions, Section 12.1 "Messages", Table, code E730 and
Section 12.2 "Response of outputs to errors".
Factory setting:
Low sensor limit •1.1
(For the low sensor limit, see Sensor Range/SENSOR_RANGE, EU_0 element, ä 54.)
Pmaxalarm Window/
PMAX_ALARM_
WINDOW
Entry
Index: 28
Data type: float
Access: auto, OOS
Customer-specific process monitoring – enter upper pressure limit.
You can use the Select Alarmtype/SELECT_ALARM_TYPE parameter to enter how the
device responds if the operating pressure overshoots the specified value.
See also these Operating Instructions, Section 12.1 "Messages", Table, code E731 and
Section 12.2 "Response of outputs to errors".
Factory setting:
High sensor limit •1.1
(For the high sensor limit, see Sensor Range/SENSOR_RANGE, EU_100 element,
ä 54.)
Temp. Eng. Unit/
TEMPERATURE_UNIT
Display
Index: 29
Data type: Unsigend16
Access: read only
Displays the temperature unit selected.
You can select the temperature unit by means of the Secondary Value Unit/
SECONDARY_VALUE_UNIT parameter ( ä 56) in the Pressure Transducer Block.
Tminalarm Window/
TMIN_ALARM_
WINDOW
Entry
Index: 30
Data type: float
Access: auto, OOS
Customer-specific process monitoring – enter lower temperature limit.
You can use the Select Alarmtype/SELECT_ALARM_TYPE parameter to enter how the
device responds if the operating pressure undershoots the specified value.
See also these Operating Instructions, Section 12.1 "Messages" Table, code E732 and
Section 12.2 "Response of outputs to errors".
Factory setting:
Lower sensor temperature operating limit – 10 K (
for the lower sensor temperature
operating limit, see Tmin Sensor/SENSOR_TEMP_LOW_LIMIT, ä 76)
Tmaxalarm Window/
TMAX_ALARM_
WINDOW
Entry
Index: 31
Data type: float
Access: auto, OOS
Customer-specific process monitoring – enter upper temperature limit.
You can use the Select Alarmtype/SELECT_ALARM_TYPE parameter to enter how the
device responds if the operating pressure overshoots the specified value.
See also these Operating Instructions, Section 12.1 "Messages" Table, code E733 and
Section 12.2 "Response of outputs to errors".
Factory setting:
Upper sensor temperature operating limit +10 K (for the upper sensor temperature
operating limit, see Tmax Sensor/SENSOR_TEMP_HIGH_LIMIT, ä 77)