Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (via local operation and FieldCare)
Endress+Hauser 109
!
Note!
1. For this level mode, the measured variables %, level, volume and mass are available. → See
also parameter description for OUTPUT UNIT (023), → ä 148.
4 Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
P01-xxxxxxxx-05-xx-xx-xx-026
Fig. 22: Calibration with reference pressure –
wet calibration
1 See Table, Step 7.
2 See Table, Step 8.
3 See Table, Step 9.
4 See Table, Step 10.
5 Select a volume unit via the OUTPUT UNIT parameter,
here l (liters) for example.
6 Select the "Dry" option by means of the CALIBRATION
MODE parameter.
7 Enter the volume value for the lower calibration point
via the EMPTY CALIB. parameter, here 0 l for example.
8 Enter the pressure value for the lower calibration point
via the EMPTY PRESSURE parameter, here 50 mbar (1
psi) for example.
9 Enter the volume value for the upper calibration point
via the FULL CALIB. parameter, here 1000 l (264 US
gal) for example.
10 Enter the pressure value for the upper calibration point
via the FULL PRESSURE parameter, here 450 mbar (7
psi) for example.
11 Result:
The measuring range is set for 0 to 1000 l (264 US gal).
Description
1000
0
V
[l]
50 450
p
[mbar]
➀
➁
➂
➃