Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
52 Endress+Hauser
Update Event/
UPDATE_EVT
Display
Index: 7
Data type: DS-73
Access: read only
The Update Event/UPDATE_EVT parameter is a structured parameter consisting of five
elements.
UNACKNOWLEDGED
This element is set to "Unacknowledged" as soon as a static parameter changes.
UPDATE_STATE
Indicates whether the change was reported.
TIME_STAMP
Displays the date and time when a static parameter was changed.
STATIC_REVISION
The revision counter is increased each time a static parameter is changed.
RELATIVE_INDEX
Displays the altered parameter in the form of the relative index. See also this Table,
"Parameter, Index" column.
Block Alarm/
BLOCK_ALM
Display, selection
Index: 8
Data type: DS-72
Access: auto, OOS
The Block Alarm/BLOCK_ALM parameter is a structured parameter consisting of five
elements.
UNACKNOWLEDGED
If the "Deactivated" option was selected for the alarm that occurred by means of the
Acknowledge Option/ACK_OPTION parameter, this alarm can only be acknowledged by
means of this element.
ALARM_STATE
Use this function to display the current block condition with information on pending
configuration, hardware or system errors.
TIME_STAMP
Displays the date and time when the alarm occurred.
SUB_CODE
Displays the reason why the alarm was reported.
VALUE
Displays the value of the corresponding parameter at the time the alarm was reported.
Transducer Directory
Entry/TRANSDUCER_
DIRECTORY
Display
Index: 9
Data type: unsigned16
Access: read only
A directory that specifies the number of transducers, and their indexes, mapped in the
Pressure Transducer Block. This parameter is only displayed in the Pressure Transducer
Block.
Display:
0: Only one transducer is mapped in the Pressure Transducer Block.
Transducer Type/
TRANSDUCER_TYPE
Display
Index: 10
Data type: unsigned16
Access: read only
Displays the Transducer Block type.
Transducer Error/
XD_ERROR
Display
Index: 11
Data type: usigned8
Access: read only
Displays the active device state.
See also these Operating Instructions, Section 12.1 "Messages".
Prerequisite:
Pressure Transducer Block
Service Transducer Block
DP Flow Transducer Block (only Deltabar S)
Collection Directory/
COLLECTION_
DIRECTORY
Display
Index: 12
Data type: Unsigned32
Access: read only
A directory that specifies the number of parameter groups (data collection), and their indexes
and DD item IDS, mapped in the Pressure Transducer Block. This parameter is only displayed
in the Pressure Transducer Block.
Display:
0: This parameter is not used.
Transducer Block, FOUNDATION Fieldbus standard parameters (all Transducer Blocks)