Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
58 Endress+Hauser
Scale Out/SCALE_OUT
Entry
Index: 36
Data type: DS-68
Access: OOS
The Scale Out/SCALE_OUT parameter is a structured parameter consisting of four elements.
EU_100
"Pressure" measuring mode; "Level easy pressure" measuring mode; "Level easy height"
measuring mode; "Level standard" measuring mode, "Linear" level mode: enter the upper
limit for the output value of the Transducer Block.
Factory setting: 100
"Level standard" measuring mode, "Pressure linearized" or "Height linearized" level mode:
Enter the maximum tank contents to be expected.
The input limits for the subsequent calibration (editing limits) are derived from the value
entered. The closer the value entered corresponds to the maximum tank content to be
expected, the more accurate the measurement result.
Factory setting: 100
"Flow" measuring mode: Enter the maximum flow of the primary device.
See also the layout sheet of the primary device. The maximum flow is assigned to the
maximum pressure you enter via the Scale In/SCALE_IN parameter, EU_100 element.
Factory setting: 1.0
EU_0
"Pressure" measuring mode; "Level easy pressure" measuring mode; "Level easy height"
measuring mode; "Level standard" measuring mode, "Linear" level mode; "Flow"
measuring mode: enter the lower limit for the output value of the Transducer Block.
"Level standard" measuring mode, "Pressure linearized" or "Height linearized" level mode:
Enter the minimum tank contents to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum tank content to be expected, the
more accurate the measurement result.
•Factory setting: 0
UNITS_INDEX
Select the unit for output scaling.
DECIMAL
Enter the number of decimal places.
!
Note!
Make sure that the unit selected by means of the Scale Out/SCALE_OUT parameter, "Units
Index" element suits the measured variable.
See also the parameter descriptions for Primary Value Type/PRIMARY_VALUE_TYPE
( ä 53) and Linearization/LINEARIZATION ( ä 57).
Damping Value/
DAMPING_VALUE
Entry
Index: 37
Data type: float
Access: auto, OOS
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the local operation,
measured value (Primary Value) and output value of the Analog Input Block react to a change
in the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specification
Pressure Transducer Block
Parameter Description