Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
70 Endress+Hauser
X-Val/LINEARIZATION_
TABLE_X_VALUE
(semiautomatic)
Index: 74
Data type: float
Access: auto, OOS
In the "Semiautomatic" entry mode, the container is filled or emptied in stages.
The X-Val/LINEARIZATION_TABLE_X_VALUE displays the measured hydrostatic pressure.
Prerequisite:
• Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Operating program
The X-Val/LINEARIZATION_TABLE_X_VALUE is saved by confirming the Y-value.
HARD handheld
Confirm X-Val/LINEARIZATION_TABLE_X_VALUE displayed.
→ See also Lin. Edit Mode/LINEARIZATION_EDIT_MODE, Line-Numb/
LINEARIZATION_TABLE_INDEX and Y-Val/LINEARIZATION_TABLE_Y_VALUE.
Y-Val/LINEARIZATION_
TABLE_Y_VALUE
Index: 75
Data type: float
Access: auto, OOS
Enter the volume, mass or %-value belonging to the X-Val/LINEARIZATION_TABLE_X_
VALUE for the linearization table.
Prerequisite:
• Table Selection/LINEARIZATION_TABLE_SELECTION = Editor table
Depending on the setting in the Lind. Measurand/LINEARIZED_MEASURAND or Comb.
Measurand/COMBINED_MEASURAND parameters, enter a volume, mass or %-value here.
→ See also table, parameter description for Lin. Edit Mode/LINEARIZATION_EDIT_MODE,
Line-Numb/LINEARIZATION_TABLE_INDEX, X-Val/LINEARIZATION_TABLE_
X_VALUE ("Manual" entry mode), X-Val/LINEARIZATION_TABLE_X_VALUE
("Semiautomatic" entry mode)
Editor Table/
LINEARIZATION_
TABLE_POST_EDIT
Index: 76
Data type: UNSIGNED8
Access: OOS
Select the function for the editor table.
Options:
• Next point: no function
• Last input point: no function
• Accept input table: save editor table as measuring table. This overwrites the old measuring
table.
• Abort: save values entered up to this point for the editor table and display next parameter.
The editor table is not activated as a measuring table.
• Insert point: see example below.
• Delete point: the current point is deleted. See example below.
Example: Add point, in this case between the 4th and 5th point for example
– Select Point 5 via the Line-Numb/LINEARIZATION_TABLE_INDEX parameter.
– Using the Editor Table/LINEARIZATION_TABLE_POST_EDIT parameter, select the
"Insert point" option.
– Point 5 is displayed for the Line-Numb/LINEARIZATION_TABLE_INDEX parameter.
Enter new values for the X-Val/LINEARIZATION_TABLE_X_VALUE and
Y-Val/LINEARIZATION_TABLE_Y_VALUE parameters.
Example: Delete point, in this case the 5th point for example
• Select Point 5 via the Line-Numb/LINEARIZATION_TABLE_INDEX parameter.
• Using the Editor Table/LINEARIZATION_TABLE_POST_EDIT parameter, select the
"Delete point" option.
• The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Factory setting:
Next point
Measuring Table/
LINEARIZATION_TABLE
_POST_VIEW
Index: 77
Data type: UNSIGNED8
Access: auto, OOS
Select the function for the measuring table.
Options:
• Next point: view next point of the measuring table.
• Last input point: view previous point of the measuring table.
• Abort: cancel measuring table display. Display next parameter.
Factory setting:
Next point
Tank Description/
LEVEL_TANK_
DESCRIPTION
Entry
Index: 78
Data type: visible string
Access: auto, OOS
Enter tank description. (max. 32 alphanumeric characters)
Factory setting:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Pressure Transducer Block
Parameter Description