Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 75
7.3.3 Service Transducer Block
Empty Calib. Level Easy/
EMPTY_CALIBRATION_
EASY
Index: 94
Data type: FLOAT
Access: OOS
Enter the height value for the lower calibration point (container empty). The unit is selected
via the Output Unit Level Easy/OUTPUT_UNIT_EASY parameter (→ ä 73).
Factory setting:
0.0
Full Pressure Level Easy/
FULL_PRESSURE_EASY
Index: 95
Data type: FLOAT
Access: OOS
Enter the pressure value for the upper calibration point (container full).
→ See also Full Calib. Level Easy/FULL_CALIBRATION_EASY.
Prerequisite:
• Calibration Mode Level Easy/CALIBRATION_MODE_EASY= Dry
Factory setting:
100.0
Empty Pressure Level
Easy/
EMPTY_PRESSURE_
EASY
Index: 96
Data type: FLOAT
Access: OOS
Enter the pressure value for the lower calibration point (container empty).
→ See also Empty Calib. Level Easy/EMPTY_CALIBRATION_EASY.
Prerequisite:
• Calibration Mode Level Easy/CALIBRATION_MODE_EASY = Dry
Factory setting:
0.0
Service Transducer Block
Parameter Description
Insert Pin No/SW_LOCK
Display
Index: 12
Data type: UNSIGNED16
For entering a code to lock or unlock operation.
!
Note!
• The -symbol on the local operation indicates that operation is locked. Parameters
which refer to how the display appears, e.g. Language/DISPLAY_LANGUAGE and Display
Contrast/DISPLAY_CONTRAST , can still be altered.
• If operation is locked by means of the DIP switch, you can only unlock operation again by
means of the DIP switch. If operation is locked by means of remote operation, you can
only unlock operation again using remote operation.
→ See also Operating Instructions for Deltabar S (BA00301P), Cerabar S (BA00302P) or
Deltapilot S (BA00372P), Section 5.6 "Locking/unlocking operation".
Options:
• Lock: Enter a number between 0 and 9999 and ≠100.
• Unlock: Enter the number 100.
Factory setting:
100
Status Locking/
STATUS_LOCKING
Display
Index: 13
Data type:UNSIGNED 8
Displays the current locking status of the device or conditions that can lock the device
(hardware locking, software locking).
Config. Recorder/
CONFIGURATION_
COUNTER
Display
Index: 14
Data type: unsigned16
Access: read only
Displays the configuration counter.
This counter is incremented by one with each change of a manufacturer-specific parameter.
The counter counts up to 65535 and then starts again at zero. Changes to parameters that
configure the local operation, such as the Language/DISPLAY_LANGUAGE parameter, do
not cause an increase in the counter value.
Pressure Transducer Block
Parameter Description