Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
78 Endress+Hauser
Counter: T > Tmax/
COUNTER_TMAX
Display
Index: 29
Data type: unsigned16
Access: read only
Displays the number of times the specified temperature range of the sensor has been
overshot. You can reset this counter via the Reset Peakhold/RESET_PEAK_HOLD
parameter.
Max. Meas. Temp./
MAX_MEASURED_
TEMP
Display
Index: 30
Data type: float
Access: read only
Displays the highest measured temperature in the sensor (peak hold indicator). You can reset
this maximum indicator via the Reset Peakhold/RESET_PEAK_HOLD parameter.
Counter: T < Tmin/
COUNTER_TMIN
Display
Index: 31
Data type: unsigned16
Access: read only
Displays the number of times the specified temperature range of the sensor has been
undershot. You can reset this counter via the Reset Peakhold/RESET_PEAK_HOLD
parameter.
Min. Meas. Temp./
MIN_MEASURED_
TEMP
Display
Index: 32
Data type: float
Access: read only
Displays the lowest measured temperature in the sensor (peak hold indicator). You can reset
this maximum indicator via the Reset Peakhold/RESET_PEAK_HOLD parameter.
Pcb Count: T > Tmax/
ELECTRONIC_OVER_
TEMP_COUNTER
Display
Index: 33
Data type: unsigned16
Access: read only
Displays the number of times the specified temperature range of the electronics has been
overshot.
Pcb Max. Temp./
ELECTRONIC_OVER_
TEMPERATURE
Display
Index: 34
Data type: float
Access: read only
Displays the highest electronics temperature measured.
Pcb Count: T< Tmin/
ELECTRONIC_UNDER_
TEMP_COUNTER
Display
Index: 35
Data type: unsigned16
Access: read only
Displays the number of times the specified temperature range of the electronics has been
undershot.
Pcb Min. Temp./
ELECTRONIC_UNDER_
TEMPERATURE
Display
Index: 36
Data type: float
Access: read only
Displays the lowest electronics temperature measured.
Service Transducer Block
Parameter Description