Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
88 Endress+Hauser
7.3.5 Display Transducer Block
Fact. U. U. Total. 2/
CUSTOMER_UNIT_
FACTOR_TOT_2
Entry
Index: 36
Data type: Float
Access: read, write, OOS
Enter the conversion factor for a customer-specific unit for totalizer 2.
→ ä 87, Totalizer Transducer Block, parameter description for Fact. U. U. Total.1/
CUSTOMER_UNIT_FACTOR_TOT_1.
Prerequisite:
• Deltabar S differential pressure transmitter
• Totalizer 2/TOTALIZER_2_VALUE = User unit
Factory setting:
1.0
Display Transducer Block
Parameter Description
Main Line Cont./
DISPLAY_MAINLINE_
CONTENT
Selection
Index: 11
Data type: unsigned8
Access: auto, OOS
Specify the contents for the main line of the local operation in the measuring mode.
Options:
• Primary value (PV)
• Main measured value (%)
• Pressure
•Flow
• Level
• Tank content
• Temperature
• Error number
• Totalizer 1
• Totalizer 2
•ISEL In1
•ISEL In2
•ISEL In3
•ISEL In4
•PID In1
The selection depends on the measuring mode chosen.
Factory setting:
Primary value (PV)
Main Data Format/
DISPLAY_MAINLINE_
FORMAT
Selection
Index: 12
Data type: unsigned8
Access: auto, OOS
Specify the number of places after the decimal point for the value displayed in the main line.
Options:
•Auto
•x.x
•x.xx
•x.xxx
• x.xxxx
• x.xxxxx
Factory setting:
Auto
Alternate Data/
DISPLAY_
ALTERNATING_VALUES
Selection
Index: 13
Data type: unsigned8
Access: auto, OOS
Switch on the "Alternating display" mode.
In this display mode, the local operation alternates between the following measured values
depending on the measuring mode selected.
– Pressure: primary value (PV), main measured value (%), pressure and temperature
– Level: primary value (PV), main measured value (%), pressure, level, tank contents and
temperature
– Flow: primary value (PV), main measured value (%), pressure, flow, temperature, totalizer
1 and totalizer 2
Options:
•Off
•On
Factory setting:
Off
DP Flow Transducer Block
Parameter Description