Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
98 Endress+Hauser
Update Event/
UPDATE_EVT
Display
Index: 20
Data type: DS-73
Access: read only
The Update Event/UPDATE_EVT parameter is a structured parameter consisting of five
elements.
ACKNOWLEDGED
This element is set to "Unacknowledged" as soon as a static parameter changes.
REPORTED
Displays the date and time when the message was generated.
TIME_STAMP
Displays the date and time when a static parameter was changed.
STATIC_REVISION
This revision counter is increased with the alarm.
RELATIVE_INDEX
Displays the altered parameter in the form of the relative index. See also this Table,
"Parameter, Index" column.
Block Alarm/
BLOCK_ALM
Display, selection
Index: 21
Data type: DS-72
Access: auto, man, OOS
The Block Alarm/BLOCK_ALM parameter is a structured parameter consisting of five
elements.
UNACKNOWLEDGED
If the "Deactivated" option was selected for the alarm that occurred by means of the
Acknowledge Option/ACK_OPTION parameter, this alarm can only be acknowledged by
means of this element.
ALARM_STATE
Use this function to display the current block condition with information on pending
configuration, hardware or system errors. The following block alarm messages are possible
with the Analog Input Block:
Simulate active
Input failure
Block config error
–Out of service
TIME_STAMP
•Displays the time when the alarm occurred.
SUB_CODE
Displays the reason why the alarm was reported.
VALUE
Displays the value of the corresponding parameter at the time the alarm was reported.
Alarm Summary/
ALARM_SUM
Display, selection
Index: 22
Data type: DS-74
Access: auto; man, OOS
The Alarm Summary/ALARM_SUM parameter is a structured parameter consisting of four
elements.
CURRENT
Displays the current status of the process alarms in the Analog Input Block.
The following alarms are possible: HiHiAlm, HiAlm, LoLoAlm, LoAlm and BlockAlm.
UNACKNOWLEDGED
Displays the process alarms not confirmed.
UNREPORTED
Displays the process alarms not reported.
DISABLED
Possibility of deactivating process alarms.