Temperature head transmitter 10 Technical Data
Endress+Hauser 55
Shock and vibration
resistance
4g / 2...150 Hz accord. to IEC 60 068-2-6
Electromagnetic
compatibility (EMC)
Interference immunity and interference emission according to EN 61 326-1
(IEC 1326) and NAMUR NE 21.
Mechanical construction
Design, dimensions Dimensions in mm
Weight approx. 40 g
Material • Housing:
PC
• Potting:
PUR
Terminals Cable up to max. 1.75 mm
2
(secure screws)
Human interface
Remote operation • Configuration:
Hand operating module DXR 275 or PC with Commubox FXA 191 and
operating software, e. g. Commuwin II
• Interface
PC interface RS232 and Commubox FXA 191
• Configurable parameters
Sensor type and connection type, engineering units (°C/°F), measurement
range, internal/external cold junction compensation, cable resistance
compensation on 2 wire connection, fault conditioning, output signal
(4...20/20...4 mA), digital filter (damping), offset, measurement point
identification + Descriptor (8 + 16 characters), output simulation,
customer specific linearisation, min./max. process value indicator function
Certificates and approvals
Ex certification For further details on the available Ex versions (ATEX, FM, CSA, usw.) please
contact your respective E+H sales organisation. All relevant data for
hazardous areas can be found in separate Ex documentation. If required,
please request copies from us or your E+H sales organisation.
CE mark The measurement system fulfills the requirements demanded by the EU
regulations. Endress+Hauser acknowledges successful unit testing by
adding the CE mark.
Further Documentation
Further Documentation • System information iTEMP
®
Temperature head transmitter (SI 008R/09/en)
• Technical information: iTEMP
®
HART
®
TMT 182 (TI 078R/09/en)
• Additional documentation for use in explosion-hazardous areas: ATEX,
FM, CSA
1. according to ASTM E988
2. according to DIN 43710
3. not for thermocouple (TC)
4. % is related to the adjusted measurement range (the value to be applied is the greater).
5. All data is related to a measurement end value.
6. according to reference conditions
R09-TMT182ZZ-06-xx-xx-001.eps