Levelflex M FMP40 FOUNDATION Fieldbus Appendix
Endress+Hauser 113
11.4 Resource block
The resource block contains the parameters used to describe physical resources of the device. It has
no linkable inputs or outputs.
11.4.1 Operation
The resource block is opened by a click on the resource line.
If the NI-FBUS Configurator is being used, a series of file tabs appears on the screen. The files can
be opened to view and/or edit the parameters in the following table. A short description of the
parameter function appears on the side of the screen. A change in the parameter is stored by pressing
the WRITE CHANGES button when the block is out of service. Press the READ ALL button to check
the values stored in the device.
11.4.2 Parameters
The function of the resource block parameters not described here can can be taken from the
FOUNDATION Fieldbus specification, see "www.fieldbus.org".
Parameter Description
TAG_DESC User description of the intended application of the block.
MODE_BLK Lists the actual, target, permitted and normal operating modes of the block.
Target: changes the operating mode of the block
Actual: indicates the current operating mode of the block
Permitted: states which operating modes are allowed
Normal: indicates the normal operating mode of the block
The possible operating modes of the resources block are:
AUTO: the block is operating as normal
OOS: the block is out of service.
If the resource block is out of service, then all blocks within the device (resource) are
forced into the same status.
RS_STATE Indicates the state of the resource block application state machine
On-line: block in AUTO mode
Standby: block in OOS mode
WRITE_LOCK Indicates the status of DIP-switch WP
LOCKED: device data can be modified
NOT LOCKED: device data can be modified
RESTART Allows a manual restart:
UNINITIALISED: no status
RUN: normal operational status
RESOURCE: resets the resource block parameters
DEFAULTS: Resets all FOUNDATION Fieldbus parameters within the
device, but not the manufacturer specific parameters.
PROCESSOR: make a warm start of the processor
BLOCK_ERROR Shows error status of software and hardware components
Out-of-Service: the block is in OOS mode
Simulation active: shows the setting of DIP-switch SIM
BLOCK_ALM Shows any configuration, hardware, connection and system problems in the lock.
The cause of the alert is to be seen in the subcode field.