Commissioning Levelflex M FMP40 FOUNDATION Fieldbus
78 Endress+Hauser
6.9 Commissioning with a FOUNDATION Fieldbus
configuration tool
!
Note!
For commissioning of the device with a FOUNDATION Fieldbus configuration tool you need to
know the INSTRUMENT_ID, which consists of the following parts:
whereby:
6.9.1 Fist setup
1. Open the configuration tool and load the device Descriptions (*.ffo, *.sym and - if required by
the tool - *.cff). Ensure you use the correct files ( ä 47).
2. The first time it is connected, the device reports as follows:
NI-FBUS-FMP-4x-en-002
3. Identify the device using the INSTRUMENT_ID and assign the desired field device tag name
(PD_TAG). Factory setting: PD_TAG = E+H_LEVELFLEX_M_XXXXXXXX
Instrument_ID = 452B481012-XXXXXXXX
452B48 ID code for Endress+Hauser
1012 ID code for Levelflex M
XXXXXXXX Instrument serial number, as printed on the nameplate