Levelflex M FMP40 FOUNDATION Fieldbus Trouble-shooting
Endress+Hauser 93
9.3 Application errors
Error Output Possible cause Remedy
A warning or alarm
has occurred
Depending on the configuration See table of
error messages
( ä 91)
1. See table of error messages
( ä 91 )
Measured value
(00) is incorrect
L00-FMP4xxxx-19-00-00-en-032
Measured distance
(008) OK?
yes
1. Check empty calibr. (005) and
full calibr. (006)
2. Check linearisation:
level/ullage (040)
max. scale (046)
diameter vessel (047)
Check table
no
An interference echo
may have been
evaluated.
yes
1. Carry out tank mapping
basic setup
No change off
measured value on
filling/emptying
L00-FMP4xxxx-19-00-00-en-033
Interference echo from
installations, nozzle
or extension on the
probe
1. Carry out tank mapping
basic setup
2. If necessary, clean probe
3. If necessary, select better
mounting position
F m/ft
E m/ft
t
D m/ft (008)
100%
0%
actual
expected
100%
0%
t
actual
expected