Commissioning Levelflex M FMP40 FOUNDATION Fieldbus
52 Endress+Hauser
6.3 Resetting the device
It is advisable to reset the device parameters before the commissioning if you want to use a device
with an unknown history.
6.3.1 Resetting the parameters of the FOUNDATION Fieldbus
function blocks
Parameters affected
All parameters of the FOUNDATION Fieldbus function blocks
L00-FMU4XXXX-02-00-00-YY-007
Performing the reset
Resource Block, parameter RESTART; select the option "defaults".
6.3.2 Resetting the parameters of the transducer blocks
"
Caution!
A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after
a reset.
!
Note!
The default values of each parameter are shown in bold in the menu overview in the appendix.
Parameters affected
All parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)
L00-FMU4XXXX-02-00-00-YY-008
Effects of the reset
All customer parameters are reset to their default values.
Customer interference echo suppression is not deleted.
Linearisation is switched to "linear", but the table values are kept. The table can be switched
back on in the "linearisation" (04) function group in the "linearisation" (041) function.
(FOUNDATION Fieldbus: Sensor Block, Parameter PARLINEARISATION (linearization))
Performing the reset
"diagnostics" (0A) function group, "reset" (0A3) function; enter "33333"
(FOUNDATION Fieldbus: Diagnostic Block, parameter PARRESET)
Endress+Hauser
Service-Parameter
Sensorblock
Diagnoseblock
Display-Block
Resource Block
AI-Block 1
AI-Block 2
PIDBlock
Arithmetik-Block
Input-Selector-Block
Signal-Charact.-Block
Integrator-Block
Endress+Hauser
Service-Parameter
Sensorblock
Diagnoseblock
Display-Block
Resource Block
AI-Block 1
AI-Block 2
PIDBlock
Arithmetik-Block
Input-Selector-Block
Signal-Charact.-Block
Integrator-Block