Technical data Levelflex M FMP40 FOUNDATION Fieldbus
98 Endress+Hauser
10 Technical data
10.1 Additional technical data
10.1.1 Input
Measured variable The measured variable is the distance between a reference point (see Fig., ä 14) and the product
surface. Subject to the input empty distance "E" (see Fig., ä 54), the level is calculated.
Alternatively, the level can be converted by means of linearisation (32 points) into other variables
(volume, mass).
10.1.2 Output
Output signal FOUNDATION Fieldbus (H1):
signal coding: Manchester Bus Powered (MBP)
data transmission rate: 31.25 KBit/s, voltage mode
Signal on alarm Error information can be accessed via the following interfaces:
Local display:
Error symbol ( ä 42)
Plain text display
Current output, signal on error can be selected (e.g. according to NAMUR recommendation NE43)
Digital interface
Linearization The linearization function of the Levelflex M allows the conversion of the measured value into any
unit of length or volume and mass or %. Linearization tables for calculating the volume in cylindrical
tanks are preprogrammed. Other tables of up to 32 value pairs can be entered manually or semi-
automatically. The creation of a linearization table with FieldCare is particularly convenient.