EasyManua.ls Logo

Endress+Hauser Levelflex M FMP40 - Page 77

Endress+Hauser Levelflex M FMP40
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning
Endress+Hauser 77
Evaluating the measurement:
The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm
and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty.
Amplitudes in the differential curve should be at a level of 0 mV when the tank is empty and lie
within the span that is specified by the probe-specific blocking distances. In order to not detect
any interference echoes, there must be no signals that exceed the echo threshold when the tank
is empty.
For partially-filled tanks, the map may only differ from the envelope curve at the position of the
level echo. The level signal is then detected unequivocally as a positive signal in the differential
curve. For detecting the level echo, the amplitude must lie above the echo threshold.
L00-FMP40xxx-05-00-00-en-025
6.8.2 User-specific applications (operation)
For details of setting the parameters of user-specific applications, see separate documentation
BA00245F/00/EN "Description of Instrument Functions" on the enclosed CD-ROM.
400.00
400.00
400.00
[mV]
[mV]
[mV]
300.00
300.00
300.00
200.00
200.00
200.00
100.00
100.00
100.00
0.00
0.00
0.00
-100.00
-100.00
-100.00
-200.00
-200.00
-200.00
-300.00
-300.00
-300.00
-400.00
-400.00
-400.00
-500.00
-500.00
-500.00
0.00
0.00
0.000.20
0.20
0.200.40
0.40
0.400.60
0.60
0.600.80
0.80
0.801.00
1.00
1.00[m]
[m]
[m]
LN
LN
LNE
E
EF
F
F
(1.00 m, -143.00 mV)
(0.98 m, 0.00 mV)
(0.99 m, -137.94 mV)
Launch pulse
Negative
probe end signal
Envelope curve
Differential curve = Envelope curve Mapping
Mapping

Table of Contents

Other manuals for Endress+Hauser Levelflex M FMP40

Related product manuals