Mounting Levelflex M FMP40 FOUNDATION Fieldbus
26 Endress+Hauser
Mounting Location
Recommended distance B wall-mounted rope
probe: ~1/6 to 1/4 of the container diameter.
Not central (2) in metallic tanks.
Not in the filling curtain (3).
Please order the probe length such that it ends
approx. 30 mm above the floor of the tank.
Temperature conditions must be met.
It is recommended that a protective cover (1)
be used, in order to protect the transmitter
against direct sunlight or rain. Mounting and
demounting are carried out simply with a
clamp ("Accessories", ä 84).
L00-FMP4xxxx-17-00-00-xx-001
B
123
Tank installations
Select the mounting location such that the
distance to internals (4) (e.g. limit switch, struts)
is > 300 mm.
Optimization options
Interference echo suppression: Measurement
can be optimised by electronically tuning out
interference echoes.
Bypass pipe and stilling well (only for liquids):
for viscosities of up to 500 cSt, a bypass pipe,
stilling well or a coax probe can be used to
prevent interference.
L00-FMP4xxxx-17-00-00-xx-002
4